8 System Control
Parameter
Description
FallRateMax
Maximum permitted rate for PV
drop.
If there is a greater drop in PV
power, electrical power must be
supplied by the battery.
RiseRateMax
Maximum permitted rate for PV
rise.
If there is a greater rise in PV
power, electrical power must be
stored in the battery.
StrThrsld
Function output offset in case of
mismatch.
Requirements:
☐ You must be logged in as Installer.
Procedure:
1. Go to Control Functions > Battery control functions > Ramp rate control via the page and menu selection.
2. Set the desired parameters (see Section 4.8.3, page 20).
8.3.3
Setting the Charge/Discharge of the Battery According to the Rise/Drop in
PV Power
The parameters of the function Energy Shifting can only be set if a battery inverter has been installed.
88
FSC20-BA-xx-20
Value
Explanation
0 kW/s to
100000 kW/s
0 kW/s to
100000 kW/s
0 kW to
100000 kW
SMA Solar Technology AG
Default
value
100 kW/
s
100 kW/
s
1 kW
User Manual