SMA Solar Technology AG
Parameter
Description
PwrAtFeedInMax
Maximum feed-in value for active
power in case of active grid con-
nection
PwrAtGridMinLoad
Minimum load value for active
power in case of active grid con-
nection
SpntOfsAbs
Function output offset in case of
mismatch
WarTrshldAbs
Warning threshold of grid's ac-
tive power
ErrTrshldAbs
Error threshold of grid's active
power
WarTrshldTm
Warning timer of grid's active
power
Error timer of grid's active power
ErrTrshldTm
Error timer of grid's active power
Requirement:
☐ You must be logged in as Installer.
Procedure:
1. Go to Control Functions > Grid control functions > Feed in protection via the page and menu selection.
2. Set the desired parameters (see Section 4.8.3, page 20).
User Manual
Value
Explanation
0 kW to
100000 kW
0 kW to
100000 kW
0 kW to
100000 kW
0 kW to
100000 kW
0 kW to
100000 kW
0.1 s to 86400 s
0.1 s to 86400 s
8 System Control
Default
value
0 kW
0 kW
0 kW
0 kW
-10 kW
10.0 s
5.0 s
FSC20-BA-xx-20
97