8 System Control
Parameter
Description
DisBatSpntLimPc
Amount of power provided by
the battery based on the maxi-
mum discharge power of the bat-
tery system
The buffered energy is released
by the storage system if too little
PV power is available. The set-
point for discharging the battery
is limited to this value.
MinDisTm
Minimum time for the battery to
provide power
The energy required must be
stored in the battery.
Requirement:
☐ You must be logged in as Installer.
Procedure:
1. Go to Control Functions > Battery control functions > Energy Shifting via the page and menu selection.
2. Set the desired parameters (see Section 4.8.3, page 20).
90
FSC20-BA-xx-20
Value
Explanation
0% to 100%
60 s to 200000 s
SMA Solar Technology AG
Default
value
10 %
1800 s
User Manual