8 System Control
Parameter
Description
Enable
Activate the Reverse Power
Protection function.
ErrTolDevMinPc
Tolerance for error detection
upon device reverse power in %
of the nominal active genset
power in kW
ErrTolDevMinTm
Timer for error output upon de-
vice reverse power in seconds.
WarTolDevMinPc
Tolerance for warning detection
upon device reverse power in %
of the nominal active genset
power in kW
WarTolDevMinTm
Timer for warning output upon
device reverse power in seconds
ErrTolTotPc
Tolerance for error detection
upon total reverse power in % of
the nominal active genset power
in kW
ErrTolTotTm
Timer for error output upon total
reverse power in seconds
WarTolTotPc
Tolerance for warning detection
upon total reverse power in % of
the nominal active genset power
in kW
WarTolTotTm
Timer for warning output upon to-
tal reverse power in seconds
Requirement:
☐ You must be logged in as Installer.
72
FSC20-BA-xx-20
Value
Explanation
Yes
Activates the function Yes
No
Deactivates the func-
tion
-100% to +100
0.1 s to 60 s
-100% to +100
0.1 s to 60 s
-100% to +100
0.1 s to 60 s
-100% to +100
0.1 s to 60 s
SMA Solar Technology AG
Default
value
-5 %
0.1 s
5 %
2 s
-5 %
0.1 s
5 %
2 s