Controlling the Fuel Save Controller

8.4.1

Configuring Setpoint Change Rate for PV inverters and Gensets

Parameter overview
Figure 42: Ramps: Settings for the setpoint change rate for inverters and gensets
Parameter
Description
GenPwrMngmtTran-
Maximum rate of active power setpoint for
sRamp
PV system in case of too low reserve power.
PvPwrAtFallRateMax
Maximum negative rate of the active power
setpoint for PV inverters in percent per sec-
ond (%/s) of related nominal inverter power
PvPwrAtRiseRateMax Maximum positive rate of the active power
setpoint for PV inverters in percent per sec-
ond (%/s) of related nominal inverter power
PvPwrRtFallRateMax
Maximum negative rate of the active power
setpoint for PV inverters in percent per sec-
ond (%/s) of related nominal inverter power
PvPwrRtRiseRateMax
Maximum positive rate of the reactive power
setpoint for PV inverters in percent per sec-
ond (%/s) of related nominal inverter power.
User Manual
Value
Default value
0%/s to 100%/s
5%/s
0%/s to 1000%/s
20%/s
0%/s to 1000%/s
5%/s
0%/s to 1000%/s
20%/s
0%/s to 1000%/s
20%/s