8 System Control
Parameter
Description
BatPwrAtFall-
Maximum negative rate of active power set-
RateMax
point for battery system related to the actual
power.
BatPwrAtRiseR-
Maximum positive rate of active power set-
ateMax
point for battery system related to the actual
power
BatPwrRtFallRateMax Maximum negative rate of reactive power
setpoint for battery system related to the ac-
tual power
BatPwrRtRiseR-
Maximum positive rate of reactive power set-
ateMax
point for battery system related to the actual
power
SlowStopRamp
Rate with which the complete system set-
points will be ramped down in case of a
stop.
Requirement:
☐ You must be logged in as Installer.
Procedure:
1. Go to Control Functions > FSC control functions > Ramps via the page and menu selection.
2. Set the desired parameters (see Section 4.8.3, page 20).
92
FSC20-BA-xx-20
SMA Solar Technology AG
Value
Default value
0%/s to 1000%/s
20%/s
0%/s to 1000%/s
20%/s
0%/s to 1000%/s
20%/s
0%/s to 1000%/s
20%/s
0 s to 3600 s
20 s