Technical data
Property
Speed
Nominal diameters DN
– SIE...BV, DIE...BV
– PBE...BV
Pipe connections
Permissible temperature min./max.
Ambient temperature min./max.
Max. permissible operating pressure
Insulation class
Protection class
Electromagnetic compatibility *)
Emitted interference in acc. with
Interference resistance in acc. with
Sound pressure level
Approved fluids
Electrical connection
PTC thermistor sensor
Speed control
Humidity
*) This is a product with limited availability according to IEC 61800-3. This product can cause radio interference in residential areas; in this case, it may be
necessary for the operator to take appropriate measures. In the case of interference, an optional filter is available.
34
The type key consists of the following elements:
Example:
SIE 204-22/11-BV(-ED)
DIE 204-22/11-BV(-ED)
PBE 204-22/11-BV(-ED)
SI
Flange-end pump as Inline pump
DI
Flange-end pump as Double pump
PB
Flange-end pump as MonoBloc pump
E
With Electronic module for electronic speed control
2
2-pole motor
04
Nominal diameter DN of the pipe connection
(for PBE...BV pressure side)
22
Nominal diameter of the impeller
11
Motor power in kW
BV
Basic Function
ED
Without differential pressure sensor
(0-10 V or 0-20 mA)
Value
2900 rpm; 1450 rpm
40; 50; 65; 100; 125; 150; 200
32; 40; 50; 65; 80; 125
Flanges PN 16
-20°C to +140°C
0 to 40°C
16 bar
F
IP 54
EN 61800-3
EN 61800-3
< 78 dB(A)
Heating water in acc. with VDI 2035
Cooling/cold water
Water/glycol mixture up to 40% vol.
Heat transfer oil
Other fluids
3~400 V ± 10%, 50 Hz
3~380 V -5% + 10%, 60 Hz
Built-in full motor protection
Built-in frequency converter
< 90%, without condensation
When ordering spare parts, make sure to state all the information
given on the pump and motor name plates.
Remarks
EN 1092-2
Residential
Industrial
Standard version
Standard version
Standard version
Only for special version
Only for special version
Pompes Salmson 03/2011