TANK FILLING
This operation must be performed whenever the available refrigerant fluid in the tank is less
than 3 kg and must in any case be performed when the "empty tank" alarm is displayed.
If gas analyzer is installed, the machine will test the purity of the refrigerant gas in the external
tank before beginning recovery (refer to Gas analyzer instruction manual)
From MAINTENANCE, select TANK FILLING, the following screen will be displayed:
Procure a tank of appropriate refrigerant (R134a/R456a or R1234yf), connect and open LP
coupler to the liquid side of the external tank and open the liquid valve, then Use the keypad to
insert the amount of refrigerant, then press ENTER to continue.
The TANK FILLING will start.
The machine will now fill the machine tank with the preset quantity ~ 500g. When the quantity
minus 500 grams is reached, the machine will stop and display:
Close the liquid valve of the external tank and press ENTER, the machine will recover the
residual refrigerant from the hoses. The refrigerant that is recovered in this phase is estimated
to be 500g but can charge depending on many factors ( the pressure of the external bottle, the
refrigerant flow or the pressure inside the internal bottle, for example). Then will display the
following screen:
INSTRUCTIONS MANUAL
TANK FILLING
MIN:600g MAX:2791g
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _
TANK FILLING
Gas charged: 122 g
Pressure -0.1 bar
TANK FILLING
Close the external valve
tank and press ENTER
-64-
ESC
ENTER
ENTER
DD/MM/YY XX:XX PM
STOP
DD/MM/YY XX:XX PM
ENTER