User Level; Versatronic Standard - Ecolab Versatronic Instrucciones De Servicio

Ocultar thumbs Ver también para Versatronic:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Device menu
10.3

User level

Users have a clear overview of the main parameters of the respective measurement and
control channel. This allows an easy and fast configuration.
The user level is only displayed in the device menu when a notification has
been performed previously by an operator or master.
(See
Open the entry dialogue by touching the display panel of a data point.
Fig. 83: Example of a user level view
10.3.1

Versatronic standard

Configuration
point
Ch. X name
Ch. X unit
(not with pH or ORP)
Ch. X type of
measurement
(Only pH and ORP)
Ch. X Scaling start
(only for
measurements with
standard signal e.g.
Cl, Cd, PA etc.)
Ch. X Scaling end
(only for
measurements with
standard signal e.g.
Cl, Cd, PA etc.)
Start ch. X Indicator
range
Ch. X end indicator
range
Ch. X Al1 alarm type
417102269 Rev. 2-08.2020
Ä Chapter 10.1 'Login / logout' on page 108.)
Selection / option
Text box
mS/cm, µS/cm
(with Cr or Ci measurement)
or text field
(with a Cl, Cd, PA measurement)
* pH standard
pH antimony
pH ISFET
* Redox (ORP)
ammonia
* = Please select only the highlighted points
-99999 bis 99999
-99999 bis 99999
-99999 to 99999
-99999 to 99999
*Inactive
* Min. Alarm
* Max. alarm
Alarm window
Inverted alarm window
* = Please select only the highlighted points
Explanation
Channel. Edit X name
Select the unit
Choosing the type of
measurement
Assignment of display
value for standard signal
lower limit (0/4mA)
Assignment of display
value for standard signal
upper limit (20mA)
Set start of indicator range 0,0000
Set end of indicator range Cr measurement, Ci
Enable Alarm 1,
Set the alarm type
138
Default
Name
Cr measurement:
µS/cm
Ci measurement:
mS/cm
Cl measurement: mg/l
pH standard
0,0000
20,000
measurement: 500,00
pH / ORP (redox)
measurement: 14,00
Cl, Cd, PA
measurement: 20,00
Inactive

Publicidad