Device menu

10.4.10 Timer

10.4.10.1 Timer
Call Timer: Device menu è Configuration è Timer èTimer 1 to 2 è Timer
Configuration
point
Timer function
Name
Behaviour after
power off
Timer time
Lead time Timer
start
Follow-up time,
timer end
Output signal
Event list entry
Event list text
Signal for timer start Choice of binary selector
Signal Timer stop
Signal for timer
maintenance
Signal for timer
restart
Signal timer
acknowledgement
Signal tolerance
band x
417102269 Rev. 2-08.2020
Selection / option
Timer
Time switch
Time switch with runtime
Up to 15 characters of text
Program stop
Continue
Restart
hh:mm:ss
0 to 9999 s
-1 to 9999 s
High
Low
Yes
No
Up to 21 characters of text
Choice of binary selector
Choice of binary selector
Choice of binary selector
Select from binary field
Select from analogue sector Select of an analogue signal which is
170
Explanation
After an external signal triggers the
timer, there is a wait of a configurable
time before the set binary value (0 or
1) is issued.
Time name
Behaviour of the timer in case the
power supply is interrupted
Time from the start of the timer until
the timer issues the set binary value
Waiting time before the timer starts
Time interval after the timer time
Special feature: If you set the "lag
time timer end" to -1 one, it never
stops.
Inversion of the timer output signal
High:Off signal is no inverted.
Low:Off signal is inverted.
Activate/deactivate event list entries
with the ON signal from "Signal timer
start"
Message text for the event list at a
signal from "Signal Timer start"
Binary signal for starting the timer
Re-triggering with "Timer Start" is only
possible if the "lead time timer start"
and the "timer time" have elapsed.
Binary signal to reset the timer
Stopping the timer timeout
Binary signal to reset and restart the
timer during the "lead time timer start"
or the "timer time"
Only with "run-on time timer end" > 0:
Binary signal for resetting the timer
during the dwell time according to the
timer end.
to be monitored with regard to its
deviation from the "tolerance band
signal w"
The timer only continues to run if the
amount of deviation is not greater
than the window width set. If the
deviation is greater than the window
width, the running timer is stopped
and the timers that have not yet
started are prevented from starting.
Default
Timer
Timer X
Program stop
00:00:00
0 sec
0 S
High
Yes
Event timer X
No selection
No selection
No selection
No selection
No selection
No selection