Device menu
Configuration
point
Alarm type
Alarm / Event List
Alarm text
Limit
Hysteresis
Window width
Alarm delay. on
Alarm delay out
417102269 Rev. 2-08.2020
Selection/configuration
Inactive
Min. alarm
Max. alarm
Alarm window
Alarm window invert.
Out
alarm
event
up to 20 characters of text
-99999 to +99999
0 to 99999
0 to 99999
0 to 999 s
0 to 999 s
154
Explanation
Choice of alarm type
Out: Alarm is not displayed
Alarm: Alarm is displayed in the
alarm bar of the display
Event: Al is only displayed in the
event list
Text which is displayed when an
alarm is in the display and/or is on
the event list.
For the limit value, an alarm is
triggered by an excess or underflow
(depending on the type of alarm)
Distance from the threshold
Alarm on =
< Thresh. - Hyst. (At minimum
alarm)
> Thresh. + Hyst. (At max. alarm)
Alarm =
> Limit (at minimum alarm)
<Limit (at max. alarm)
Width of the alert window (in case
of alarm type "alarm window") or in
which no alarm is triggered the
window, (at the alarm type "inverted
Alarm window")
Time delay between occurrence of
the alarm condition and the alarm
turning on
Time delay between end of the
alarm set to on and the alarm
turning off
Default
inactive
Alarm
Alarm 1 Temp.
Input 1
0,00
0,00
0,00
0 sec
0 sec