SA.11
PHOTO_1 inhibition
The function inhibits the intervention of the photocells on both the opening
and closing manoeuvres, in the zone between the detection point and
the complete closing point. During the motor stroke automatic learning
manoeuvre (SE.03), the trigger of the photocells during the door closing
movement defi nes the inhibition start point. It is necessary that the photocell
to be inhibited is connected as PHOTO_1.
SA.12
Automatic closing (TCA) after obstacle during closing
In case of full reversal (SA.08=000) during a closing manoeuvre, it determines
how the automation will perform the TCA automatic re-closing manoeuvre.
Note: valid only for obstacles detected through the SAFETY mode or the
anti-crushing function.
TIMES parameters (
tI.01
Automatic closing time (TCA)
Adjusts the time for automatic closing
tI.02
Pedestrian automatic closing time (TCA_PED)
Adjusts the time for automatic pedestrian closing
tI.03
Opening pre-manoeuvre fl ashing time
Adjusts the pre-fl ashing time before an opening manoeuvre.
tI.04
Closing pre-manoeuvre fl ashing time
Adjusts the pre-fl ashing time before a closing manoeuvre.
tI.05
Not Used
tI.06
Not Used
tI.07
COURTESY Time
Adjusts the time for the COURTESY light.
tI.08
ELOCK_M1 Time
Adjusts the activation time for the ELOCK_M1 / BOOST_M1 output, or the
deactivation time of the ELOCK_INV_M1 output.
tI.09
Not Used
tI.10
Not Used
tI.11
Not Used
tI.12
Not Used
tI.13
Not Used
tI.14
Not Used
tI.15
Not Used
tI.16
AUX_1 Time
Adjusts the activation time for the AUX_1 output, if timer-controlled.
tI.17
AUX_2 Time
Adjusts the activation time for the AUX_2 output, if timer-controlled.
tI.18
Not Used
tI.19
Failed closing alarm time
Time used for the STATUS outputs confi gured as CLOSURE_FAILED: once
this time has elapsed, if the automation is not in the closing position, the
output is activated.
Note: Functions regardless of the presence of the TCA (tI.01) or TCA_PED
(tI.02).
)
NET724 EVO
000
000
• 000: Inhibition deactivated
•
001:
Inhibition
active
photocells are always ignored in the
zone between the detection point
and the closing point)
000
000
• 000: Always performs automatic
re-closing
• 001:
Attempts 1 automatic re-
closing
• 002:
Attempts 2 automatic re-
closing manoeuvres
• 003:
Attempts 3 automatic re-
closing manoeuvres
• 004: Inhibits automatic re-closing
Default
Default
TYPE 00
TYPE 04
000
000
• 000: Disabled
• >000: Active for the set time
(1s..................255s)
000
000
• 000: Disabled
• >000: Active for the set time
(1.......255s)
(1.......255min - ONLY TYPE 04)
000
000
(0s..................10s)
000
000
(0s..................10s)
060
060
0s..................255s
002
002
(1s..................10s)
100
100
(0s..................255s)
100
100
(0s..................255s)
010
010
(1min..................255min)
(the
49