Error Diagnosis
Display COMBIVIS
A.nOL
no ABN.STOP overload
A.nOL2 no ABN.STOP overload 2
A. OH
A.STOP overheat pow.mod
A.OH2
ABN.STOP motor protect.
GB
A.OHI
ABN.STOP overheat int.
A. OL
ABN.STOP overload
GB
A.OL2
ABN.STOP overload 2
A.PrF
ABN.STOP prot. rot. for.
A.Prr
ABN.STOP prot. rot. rev.
A.SbuS ABN.Bus synchron
A.SEt
ABN.STOP set
A.SLF
ABN.Software limit switch forward
A.SLr
ABN.Software limit switch reverse
GB- 34
Value Meaning
98
Warning: no more overload, OL counter has reached 0 %.
101
The cooling time after "Warning! Overload during standstill"
has elapsed. The warning message can be reset.
89
A level can be defined, when it is exceeded this warning is
output. A response to this warning can be programmed (see
chapter 6.7 "Response to errors or warning messages").
97
Warning: electronic motor protective relay has tripped. The
response to this warning can be programmed (see chapter
6.7 "Response to error or warning messages").
87
The temperature in the interior of the inverter lies above the
permissible level. The switch off time was started. The
programmed response to this warning message is executed
(see chapter 6.7 "Response to errors or warning
messages").
99
A level between 0 and 100 % of the load counter can be
adjusted, when it is exceeded this warning is output. The
response to this warning can be programmed (see chapter
6.7 "Response to errors or warning messages").
100
The warning is output when the standstill continuous current
is exceeded (see technical data and overload
characteristics). The response to this warning can be
programmed (see chapter 6.7 "Response to errors and
warning messages"). The warning message can only be
reset after the cooling time has elapsed and A.nOL2 is
displayed.
94
The drive is driven onto the right limit switch. The response
to this warning can be programmed (see chapter 6.7
"Response to errors and warning messages").
95
The drive is driven onto the left limit switch. The response to
this warning can be programmed (see chapter 6.7
"Response to errors and warning messages").
103
Synchronization over sercos-bus not possible. The response
to this warning can be programmed (see chapter 6.7
"Response to errors and warning messages").
102
Warning: set selection: It has been attempted to select a
locked parameter set. The response to this warning can be
programmed (see chapter 6.7 "Response to errors or
warning messages").
104
The target position lies outside of the limit defined with the
right software limit switch. The response to this warning can
be programmed (see chapter 6.7 "Response to errors or
warning messages").
105
The target position lies outside of the limit defined with the
left software limit switch. The response to this warning can
be programmed (see chapter 6.7 "Response to errors or
warning messages").