Error Diagnosis; Status Messages - KEB COMBIVERT F5 Serie Manual De Instrucciones

Ocultar thumbs Ver también para COMBIVERT F5 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 143
3.

Error Diagnosis

Display COMBIVIS

Status Messages

bbL
base block
bon
close brake
boFF
open brake
Cdd
calculate drive
dcb
DC brake
dLS
low speed / DC brake
FAcc
forward acceleration
Fcon
forward constant
FdEc
forward deceleration
HCL
hardware current limit
IdAtA
invalid Data
LAS
LA stop
LdS
Ld stop
LS
low speed
nO_PU power unit not ready
noP
no operation
PA
positioning active
PLS
low speed / power off
PnA
position not reachable
POFF
power off function
POSI
positioning
rAcc
reverse acceleration
At KEB COMBIVERT error messages are always represented with an
„E." and the appropriate error in the display. Error messages cause the
immediate deactivation of the modulation. Restart possible only after
reset.
Malfunction are represented with an „A." and the appropriate message.
Reactions to malfunctions can vary.
In the following the display and their cause are described.
Value Meaning
76
Power modules for motor de-excitation locked
85
Brake control, brake engaged (see chapter 6.9)
86
Brake control, brake released (see chapter 6.9)
82
Measurement of the motor stator resistance
75
Motor is decelerated by a DC-voltage at the output.
77
Modulation is switched off after DC-braking (see chapter 6.9
„DC-Braking").
64
Acceleration with the adjusted ramps in clockwise direction
of rotation.
66
Acceleration / deceleration phase is completed and it is
driven with constant speed / frequency in clockwise direction
of rotation.
65
It is stopped with the adjusted ramp times in clockwise
direction of rotation.
80
The message is output if the output current reaches the
hardware current limit.
-
The parameter address adjusted for this parameter value is
invalid.
72
This message is displayed if during acceleration the load is
limited to the adjusted load level.
73
This message is displayed if during deceleration the load is
limited to the adjusted load level or the DC-link current to the
adjusted voltage level.
70
No direction of rotation pre-set, modulation is off.
13
Power circuit not ready or not identified by the control.
0
Control release (terminal ST) is not switched.
122
This message is displayed during a positioning process.
84
No modulation after Power-Off
123
The specified position cannot be reached within the pre-set
ramps. The abort of the positioning can be programmed.
78
Depending on the programming of the function (see chapter
6.9 „Power-off Function") the inverter restarts automatically
upon system recovery or after a reset.
83
Positioning function active (F5-G).
67
Acceleration with the adjusted ramp times in anti-clockwise
direction of rotation.
Error Diagnosis