DC-braking / Mode
DC-braking / Time
With DC-braking the motor is not decelerated by the ramp. Quick braking
is caused by D.C. voltage, which is applied onto the motor winding. This
parameter determines how the dc-braking is triggered.
Value
Activation
0
DC-braking; deactivated
1
DC-braking; at switch off of the direction of rotation and
upon reaching 0Hz. The braking time is CP.23 or until the
next direction of rotation.
2*
DC-braking; as soon as setting for the direction of rotation
is absent.
3*
DC-braking; as soon as the direction of rotation changes or
is absent.
4*
DC-braking; on disabling the direction of rotation and if the
real frequency falls below 4 Hz.
5*
DC-braking; when the real frequency falls below 4 Hz.
6*
DC-braking; as soon as the set value falls below 4 Hz.
7*
DC-braking; when input I4 is switched. Braking time depends
on the real frequency. At control circuit B = value "0"
8
DC-braking; as long as input I4 is switched. At control circuit
B = value "0"
9
DC-braking; after switching on the modulation on.
* Braking time depends on the actual frequency.
Adjustment range:
Resolution:
Factory setting:
Note:
If the braking time depends on the actual frequency (CP.22 = 2...7), it is
calculated as follows:
CP.23 x f
t
=–––––––––
Breal
100 Hz
Otherwise the braking time corresponds to CP.23.
Adjustment range: 0,00...100,00 s
Resolution:
Factory setting:
Operation of the Unit
0...9
Enter-Parameter
real
100 Hz
0,01 s
10,00 s
1
7
f
f
real
t
CP.23
Breal
GB - 19