Operation of the Unit
Relay output 1 / Function
Relay output 2 / Function
GB
GB
GB- 24
CP.31 and CP.32 determine the function of the two outputs.
CP.31 for relay output 1 (terminal X2A.24...X2A.26)
CP.32 for relay output 2 (terminal X2A.27...X2A.29)
The switching level of CP.31 is 100,00.
The switching level of CP.32 is CP.33!
Value Function
0
No function (generelly off)
1
Generelly on
2
Run signal; also by DC-braking
3
Ready signal (no error)
4
Fault relay
5
Fault relay (no auto-reset)
6
Warning or error message at abnormal stopping
7
Overload alert signal
8
Overtemperature alert signal power modules
9
External Overtemperature alert signal motor
10
Only application-mode
11
Overtemperature alert signal interior OHI
12
Cable breakage 4...20 mA on analog input 1
13
Only application-mode
14
Max. constant current (stall, CP.25) exceeded
15
Max. ramp current (LA-Stop CP.24) exceeded
16
DC-braking active
17-19 Only application-mode
20
Actual value=set value (CP.3=Fcon, rcon; not at noP, LS error,SSF)
21
Accelerate (CP.3 = FAcc, rAcc, LAS)
22
Decelerate (CP.3 = FdEc, rdEc, LdS)
23
Real direction of rotation = set direction of rotation
24
Utilization (CP.6) > 100% (only CP.31)
25
Active current > switching level (only CP.32)
26
Intermediate circuit voltage (CP.7) > switching level (only CP.32)
27
Real value (CP.1) > switching level (only CP.32)
28
Set value (CP.2) > switching level (only CP.32)
29/30 Only application-mode
31
Absolut set value on AN1 > switching level (only CP.32)
32
Absolut set value on AN2 > switching level (only CP.32)
33
Only application-mode
34
Set value on AN1 > switching level (only CP.32)
35
Set value on AN2 > switching level (only CP.32)
36-39 Only application-mode
40
Hardware current limit activated
41
Modulation on-signal
42-43 Only application-mode
44
Inverter status (CP.3) = switching level
45
Heat sink temperatur > Level