Relay output 2 /
Switching level
Value Function
46
Motor temperatur > Level
47
Ramp output frequency > Level
48
Apparent current (CP.4) > Level
49
Clockwise rotation (not at noP, LS, abnormal stopping, error)
50
Counter clockwise (not at noP, LS, abnormal stopping, error)
51-62 Only application-mode
63
Absolut ANOUT1 > switching level
64
Absolut ANOUT2 > switching level
65
ANOUT1 > switching level
66
ANOUT2 > switching level
67-69 Only application-mode
70
Driver voltage active (safety-relay)
71-72 Only application-mode
73
Absolute active power
74
Active power
75-78 Only application-mode
Factory setting CP.31:
Factory setting CP.32:
Note:
This parameter determines the switching point for the relay output 2
(CP.32). After the switching of the relay, the value can move within a
window (hysteresis), without the relay dropping off. Since the operator
can display only 5 characters, the last digits are not represented in the
case of higher values.
Adjustment range:
Resolution:
Factory setting:
Hysteresis:
Frequency:
Intermediate circuit voltage:
Analog set value:
Active current:
Temperature:
Operation of the Unit
27
Enter-Parameter
-30000,00...30000,00
0,01
4,00
0,5 Hz
1 V
0,5 %
0,5 A
1 °C
4
GB - 25