9.9
PROGRAMMING THE ADDITIONAL INPUTS
In addition to the standard inputs with dedicated terminal, e.g. fuel reserve, low engine oil pressure, overheating of engine, etc.
(refer to the electric panel diagram), you can choose between three other inputs identified below as "IN AUX1, IN AUX2, IN
AUX3".
FUNCTION
Work mode
"Work mode IN AUX 1"
Work mode
"Work mode IN AUX 2"
Work mode
"Work mode IN AUX 3"
* Notes:
- AUX 1, AUX 2: Digital inputs of the X1 terminals of the electric panel for connecting the device in relation to the ground.
- AUX 3: Digital input of the terminals of the control unit's printed circuit board, for connecting the ground reference device.
- Remote start command: In this case the diesel pump starts when the status of the input signal changes and turns off when
this returns to its initial condition.
IMPORTANT: All the "IN AUX2, IN AUX3" programmable inputs are disabled and therefore set at "000" by default.
9.10
PROGRAMMING THE RELAY OUTPUTS
In addition to the "dedicated relay" status outputs, e.g. automatic mode disabled, no start, pump running, control fault, fuel
reserve, etc., and the "alarm summary relay" (refer to the electric panel diagram), there are two other status relays, "OUT AUX
1, OUT AUX 2" for the programmed inputs "IN AUX1, IN AUX2, IN AUX3".
IMPORTANT:
The relay is enabled and closes the contact when there is an alarm.
SELECTABLE
DEFAULT
FIELDS
VALUES
000 / 015
015
000 / 015
002
000 / 015
000
000 = Disabled
001 = AUX 1 input alarm
004 = Heater / Battery charger alarm
005 = Remote start command
015 = Pump pressure alarm (NO)
000 = Disabled
002 = AUX 2 input alarm
004 = Heater / Battery charger alarm
005 = Remote start command
015 = Pump pressure alarm (NC)
000 = Disabled
003 = AUX 3 input alarm
004 = Heater / Battery charger alarm
005 = Remote start command
015 = Pump pressure alarm (NC)