Lowara GEMK Serie Instrucciones Para La Instalación Y El Uso página 122

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

N.B.: Refer to the diagram provided with the electric panel for the numbers of the terminals
X1 – STATUS RELAY TERMINALS
CODE
DESCRIPTION
OUT AUX1
Output enabled by alarm programmed in set-up
OUT AUX2
Output enabled by alarm programmed in set-up
Output enabled if the "IN RIS." input is connected to ground
OUT RIS.
Alarm summary output. Output enabled by a minimum of one of the following alarms:
- Automatic operation disabled
- Motor running
- Fault with MP06 control card
- Engine no start
- Low level of fuel
- Low engine oil pressure
- High motor Temperature
ALARM
- No AC voltage
- Low Current Battery 1 or 2
- Low speed motor
- Over-revving of engine (escape)
- Triggering of Heater and/or Battery Charger protection
- Signalling of input IN AUX1
- Signalling of input IN AUX2
- Signalling of input IN AUX3
- Fuel reserve
NO AUTO
Output enabled when Switch is not in Automatic position
NO START
Output enabled after 6 failed attempts at automatically starting the engine
MOTOR ON
Output enabled when the engine is running
Output enabled by these alarms of the control unit:
FAULT NC
- software alarm
- hardware alarm
FAULT NO
- No Vdc current alarm
NO contact on the terminal block of the control unit
COM
Common terminal for relay outputs
Electrical characteristics of the digital outputs (status relay or signalling potential free contacts): Max 1A (30Vdc,
250Vac)
N.B.: Refer to the diagram provided with the electric panel for the numbers of the terminals
A qualified technician must wire the control panel correctly with reference to the wiring diagram
provided.
Here you can note down the necessary data as shown on the rating plate. Specify this data when you call for service.
Engine type (engine rating plate)
Serial number of electric panel (plate on metal structure)
Engine serial number (engine rating plate)
Pump type (pump rating plate)
Installation date
122
789-101

Publicidad

Tabla de contenido
loading