I/O terminals (versions 3~)
Item
Description
Fault signal C
25 COM - error
status relay
NO
24 NO - error status
relay
Motor
C
23 Common contact In case of
running
NO
22 Normally open
signal
contact
Auxiliary
15V 21 Auxiliary voltage
Voltage
supply +15 VDC
Supply
Analog input
S+
20 Actuator mode 0-
10 V input
0-10V
S-
19 GND for 0-10 V
input
External
P1+ 18 Power supply
Pressure
external sensor
sensor [also
+15 VDC
Differential]
P1-
17 External sensor
4-20 mA input
External
P2+ 16 Power supply
pressure
external sensor
sensor
+15 VDC
P2-
15 Sensor 4-20 mA
input
External
Start 14 External ON/OFF
Start/Stop
input
Stop 13 External ON/OFF
input reference
External
LoW+ 12 Lack water input Default short
Lack of
LoW- 11 Low water
Water
reference
Comm. Bus B2
10 RS485 port 2:
RS485-2N B (-)
active only with
optional module
A2
9 RS485 port 2:
RS485-2P A (+)
active only with
optional module
GND 8 Electronic GND
Comm. Bus B1
7 RS485 port 1:
RS485-1N B (-)
A1
6 RS485 port 1:
RS485-1P A (+)
GND 5 Electronic GND
Comments
In case of
power cables:
use the M20
cable gland
power cables:
use the M20
cable gland
15VDC, Ʃ
max. 100 mA
0÷10 VDC
GND,
electronic
ground (for
S+)
15VDC, Ʃ
max. 100 mA
4÷20 mA
15VDC, Ʃ
max. 100 mA
4÷20 mA
Default short
circuited.
Pump
enabled to
RUN
circuited.
Lack of water
detection:
enabled
RS 485 port2
for external
comm.
ACT, HCS
control mode:
RS 485 port 1
for external
comm.
Control mode
MSE, MSY:
RS 485 port 1
for multi-
pump
systems
5
Operation
In case of co-existance of two or more of the following
conditions:
• high ambient temperature
• high water temperature
• duty points insisting on unit maximum power
• persisting undervoltage of mains,
the lifespan of the unit could be shortened and/or
derating could occur. Contact Xylem or the Authorised
Distributor for further information.
5.1
Wait times
WARNING: Electrical hazard
Contact with electric components may cause
death, even after the unit has been switched
off. Before any interventions on the unit, the
network voltage and any other input voltages
must be disconnected for the minimum time
indicated in the table.
Wait times
e-SM Drive model
103, 105, 107, 111, 115
303, 305, 307, 311, 315, 322 5
WARNING: Electrical hazard
Frequency converters contain DC-link
capacitors that can remain charged even
when the frequency converter is not powered.
To avoid electrical hazards:
• Disconnect the AC power supply
• Disconnect all types of permanent magnet
motors
• Disconnect all DC-link remote power
supplies, including the battery backups, the
Uninterrupted Power Supply units and the
DC-link connections to other frequency
converters
• Wait for the capacitors to discharge
completely before carrying out any
maintenance or repairs; see the table for
the waiting times.