Hitecsa EQPL-B 4360 Manual Del Operador página 236

Enfriadoras de agua y bombas de calor reversibles monobloque con condensación por aire y refrigerante ecológico r410a. serie con compresores herméticos scroll
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Model EQPHBSS
Nominal cooling capacity (*)
EER
ESEER +
Nominal cooling capacity (*) (°) EN 14511:2013
EER (*) (°) EN 14511:2013
ESEER EN 14511:2013
Nominal heating capacity (**)
COP
Nominal heating capacity (**) (°) EN 14511:2013
COP (*) (°) EN 14511:2013
Sound pressure (***) (*)
Sound power (****) (*)
Scroll/step compressor
Circuits
Fans
Fan nominal air flow
Heat exchanger
Heat exchanger nominal flow water side (*)
Water side heat exchanger nominal pressure drops (*) kPa
Residual head P1 (*)
Residual head P2 (*)
Residual head ASP1 (*)
Residual head ASP2 (*)
Tank water content (ASP1/ASP2)
Nominal heating capacity RC100 (±)
Nominal flow rate/pressure drop RC100 (±)
Nominal heating capacity DS (±)
Nominal flow rate/pressure drop DS (±)
Amount of R410A refrigerant
Polyester oil charge
Electrical data
Absorbed power in summer mode (*) (■)
Absorbed power in winter mode (**) (■)
Pump absorbed power (P1/ASP1) / (P2/ASP2)
Electrical power supply
Auxiliary electrical/control power supply
Summer operation nominal current (*) (■)
Maximum current (■)
Starting current (■)
Starting current with SFS (■)
Pump absorbed current (P1/ASP1) / (P2/ASP2)
Dimensions
Height (a)
Width (b)
Length (c)
Heat exchanger inlet/outlet connections and RC100
DS inlet/outlet connections
Weight
(*) Under the following conditions: condenser
inlet air temperature 35°C; chilled water
temperature 7°C; temperature differential at
evaporator 5 K; evaporator scaling factor equal
to 0.35x10-4 m2 K/W.
(**) In the following conditions: Evaporator inlet
water temperature 7°C B.S., 6°C B.U.; hot
water temperature 45°C; temperature
differential at condenser 5 K; fouling factor
equal to 0.35x10-4 m2 K/W.
(***) Sound pressure level in dB(A) referring to
a 10 m distance from the unit, in free field and
directionality factor equal to Q=2. The noise
data refers to the units without the electric
pump
ALLEGATI / ENCLOSED DOCUMENTS / ANNEXES / ANLAGEN / ANEXOS
4385
4415
kW
338
368
2,68
2,57
4,70
4,69
kW
337,3
367,2
2,66
2,55
4,05
4,04
kW
368
404
3,26
3,23
kW
368,8
404,9
3,24
3,22
dB(A)
53,5
53,5
dB(A)
86
86
4/4
4/4
2
n° x kW
8x0,6
8x0,6
m³/h
90000
87500
Type
m³/h
58,1
63,3
21
22
kPa
129
121
kPa
168
160
kPa
125
117
kPa
164
156
l
700
700
kW
462
516
79,4/40
88,7/45
m³/h / kPa
kW
88
98
7,6/5
8,4/6
m³/h / kPa
Kg
63
92
Kg
20,8
20,8
4385
4415
kW
126
143
kW
113
125
kW
4,0/5,5
4,0/5,5
V-ph-Hz
V-ph-Hz
A
207
235
A
255
295
A
481
491
A
366
384
A
7,6/10,5 7,6/10,5
4385
4415
mm
2450
2450
mm
2260
2260
mm
4840
4840
Ø
DN80 VIC DN80 VIC DN80 VIC DN100 VIC DN100 VIC DN100 VIC DN100 VIC DN100 VIC
2" VIC
2" VIC
Ø
Kg
3395
3565
(****) Sound power level in dB(A) on the basis
of measurements taken in accordance with UNI
EN- ISO 9614 and Eurovent 8/1 Standards The
noise data refers to the units without the electric
pump
(±) Recovery unit heating capacity Conditions
referring to the unit operating with chilled water
temperature 7°C, differential temperature due to
evaporation of 5 K, hot water temperature
produced equivalent to 40/45°C (RC100)
50/60°C (DS). NB. With heat pumps operating
in winter mode with DC active, the heating
capacity available is decreased from the portion
supplied to the desuper- heater.
237
4460
5525
6570
402
454
485
2,51
2,62
2,49
4,63
4,80
4,72
401,1
453
483,9
2,49
2,6
2,47
3,99
4,14
4,09
440
492
534
3,24
3,22
3,22
441
493,2
535,3
3,22
3,2
3,2
54,5
54,5
54,5
87
87
87
4/4
5/5
6/6
2
2
2
8x0,6
10x0,6
10x0,6
87500
109000
109000
Plates/Shell and tube (STE accessory)
69,1
78,1
83,4
23
25
25
150
133
124
208
193
185
146
127
117
203
187
178
700
1000
1000
571
642
698
98,2/47 110,4/53 120/54 131,2/60 140,3/48 147/54
107
121
129
9,2/7
10,4/8
11,1/8
94
112
116
20,8
33
46
4460
5525
6570
160
173
195
136
153
166
5,5/7,5
5,5/7,5
5,5/7,5
400 – 3 – 50
230 – 1 – 50 / 24 – 1 – 50
263
284
320
313
369
401
536
591
627
417
472
512
10,5/14,5 10,5/14,5 10,5/14,5 10,5/14,5 10,5/14,5 10,5/14,5
4460
5525
6570
2450
2450
2450
2260
2260
2260
4840
5940
5940
2" VIC
2" VIC
2" VIC 2"1/2 VIC 2"1/2 VIC 2"1/2 VIC
3615
4310
4520
(■) Absorbed current/absorbed power value
without electric pump.
The peak current refers to the unit's most heavy
duty operating conditions.
(°) Data calculated in accordance with EN
14511:2011 under nominal conditions.
The refrigerant charge values are indicative.
Refer to the serial number plate
6625
6665
6700
522
580
603
2,31
2,56
2,53
4,70
4,67
4,67
520,8
578,9
601,7
2,29
2,54
2,51
4,07
4,05
4,05
597
630
660
3,23
3,26
3,25
598,6
631,4
661,6
3,21
3,25
3,23
54,5
55,5
56,5
87
88
89
6/6
6/6
6/6
2
2
2
10x0,6
12x0,6
12x0,6
109000
131000
131000
89,7
99,7
103,7
27
23
25
119
113
97
146
141
122
111
103
86
138
131
111
1000
1000
1000
763
816
855
145
154
160
12,5/9
13,2/9
13,8/8
116
146
146
46
46
46
6625
6665
6700
226
227
238
185
193
203
5,5/7,5
5,5/7,5
5,5/7,5
371
373
391
461
483
497
687
705
720
552
585
600
6625
6665
6700
2450
2450
2450
2260
2260
2260
5940
6840
6840
4550
5210
5240
2

Publicidad

Tabla de contenido
loading

Tabla de contenido