Enfriadoras de agua y bombas de calor reversibles monobloque con condensación por aire y refrigerante ecológico r410a. serie con compresores herméticos scroll
If the water inlet temperature to the condensers is lower than the permitted values, it is recommended to use a three-way modulating valve to guarantee
the minimum water temperature required.
Permitted temperature differentials through the heat exchangers
○ Evaporator temperature differentialAT = 3 ÷ 8°C with "Standard" set-ups. However, consider the minimum and maximum flow rates reported in the
tables "Water flow rate limits". The maximum and minimum temperature differentials for "Pump" and "Tank&Pump" set-ups are related to the
performance of the pumps, which must always be checked by means of the Up to Date selection software.
Evaporator water flow rate limits
Type of heat exchanger
Version B-S
4360
m3/h
4390
m3/h
4435
m3/h
5500
m3/h
6540
m3/h
6590
m3/h
6635
m3/h
6670
m3/h
7730
m3/h
8790
m3/h
8830
m3/h
8860
m3/h
Type of heat exchanger
Version T-SS
4385
m3/h
4415
m3/h
4460
m3/h
5525
m3/h
6570
m3/h
6625
m3/h
6665
m3/h
6700
m3/h
7760
m3/h
8820
m3/h
8870
m3/h
8920
m3/h
Recovery water flow rate limits
Type of heat exchanger
Version B-S
4360
m3/h
4390
m3/h
4435
m3/h
5500
m3/h
6540
m3/h
6590
m3/h
6635
m3/h
6670
m3/h
7730
m3/h
8790
m3/h
8830
m3/h
8860
m3/h
RC100:
•
Hot water temperature produced 30÷54°C for versions B-S / 30÷56°C for versions T-SS;
•
The minimum inlet water temperature admitted is equal to 20°C
DS:
•
Produced hot water temperature 50÷70°C with admitted water temperature differential 5÷10 K
•
The minimum inlet water temperature admitted is equal to 40°C