Descargar Imprimir esta página

Acondicionador De Alimentación Auxiliar - GE EntelliGuard G Serie Manual De Instalación, Funcionamiento Y Mantenimiento

Interruptor automático de bastidor

Publicidad

EntelliGuard G
Instruction sheet
4
.4
4.4.11
Voltage Conditioners
Function:
Provides isolated bus voltage signal to each trip
unit by stepping down the potential to 1.767VAC
also provides transient suppression. Voltage
conditioners are necessary to allow bus voltage
sense by trip units connected to same bus
voltage.
Specifics: Input:
GMPU1:
50/60Hz 220-230VAC
GMPU2:
50/60Hz 380-400VAC
GMPU3:
50/60Hz 240-250/277-290/415VAC
Output from the module:
GMPU1:
Input: 50Hz, 230VAC
Output: 1.767VAC
GMPU2:
Input: 50Hz, 400VAC
Output: 1.767VAC
GMPU3:
Input: 50Hz, 250 (option1) VAC
Output: 1.767VAC
Input: 50Hz, 290 (option2) VAC
Output: 1.767VAC
Input: 50Hz, 415 (option3) VAC
Output: 1.767VAC
GMPU4
Input:
50Hz, 690VAC, Delta connected
Output: 1.767VAC
Application:
3 sets of voltage conditioners are required
!
for each voltage sensing location.
The max. Wire length from voltage
!
conditioners to trip device is 7meter.
Use AWG16 wire (1,5 mm²).
!
Connection diagram |
Esquema de ligações
For 3 Phase 3-wire system |
Para sistemas de 3 fases a 3 fios Para sistemas de 3 Fases 3 hilos
Signals to EntelliGuard trip unit
Sinais para a unidade de disparo Entelliguard
Señales a la unidad de protección Entelliguard
VC
V+
V-
V+
EntelliGuard
---
---
L
N
L1
4.4-18
ACCESSORIES
4.4.11 Acondicionador de
alimentação auxiliar
Função
Proporciona tensão de alimentação isolada à
unidade de disparo reduzindo a tensão a 1,767V
CA, também proporciona supressão de
transitórios. É necessária para acondicionar a
alimentação de rede num sinal que a unidade
de protecção possa utilizar de forma segura.
Detalhes: Entrada:
GMPU1: 50/60Hz 220-230V CA
GMPU2: 50/60Hz 380-400V CA
GMPU3: 50/60Hz 240-250/277-290/415V CA
Saída do módulo:
GMPU1: Entrada: 50Hz, 230V CA
Saída: 1.767VCA
GMPU2: Entrada: 50Hz, 400V CA
Saída: 1.767V CA
GMPU3: Entrada: 50Hz, 250 (opção 1) V CA
Saída: 1.767V CA
Entrada: 50Hz, 290 (opção 2) V CA
Saída: 1.767V CA
Entrada: 50Hz, 415 (opção 3) V CA
Saída: 1.767V CA
GMPU4 Entrada: 50Hz, 690V CA, ligação estrela
Saída: 1.767V CA
Aplicação:
- Necessitam-se 3 acondicionadores de
alimentação para cada ponto de detecção de
tensão
- O máximo comprimento de cabo entre os
acondicionadores e a unidade de protecção é
de 7m.
- Utilize cabo AWG16 (1,5 mm²).
|
Esquema de conexionado
|
VB
VA
V-
V+
EntelliGuard
EntelliGuard
---
---
---
---
L
N
L
L2
L3
Folha de Instruções
-----------------------------------------------------------------------------------
Connection diagram |
For 3 Phase 4-wire system |
Signals to EntelliGuard trip unit
Sinais para a unidade de disparo Entelliguard
Señales a la unidad de protección Entelliguard
GND
VA
V-
1
2
EntelliGuard
---
---
N
3
4
L1
Inputs 3 phase 50/60 Hz Phase sequence L1, L2, L3
Entrada 3 Fases 50/60 Hz, Sequência de fases L1, L2, L3
Entrada 3 Fases 50/60 Hz, Secuencia de fases L1, L2, L3
Hoja de instrucciones
4.4.11 Acondicionador de
alimentación auxiliar
Función
Proporciona tensión de alimentación aislada a la
unidad de protección reduciendo la tensión a
1,767V CA, también proporciona supresión de
transitorios. Son necesarios para acondicionar la
alimentación de red en una señal que la unidad
de protección pueda utilizar de forma segura.
Detalles: Entrada:
GMPU1: 50/60Hz 220-230V CA
GMPU2: 50/60Hz 380-400V CA
GMPU3: 50/60Hz 240-250/277-290/415V CA
Salida del módulo:
GMPU1: Entrada: 50Hz, 230V CA
Salida: 1.767VCA
GMPU2: Entrada: 50Hz, 400V CA
Salida: 1.767V CA
GMPU3: Entrada: 50Hz, 250 (opción 1) V CA
Salida: 1.767V CA
Entrada: 50Hz, 290 (opción 2) V CA
Salida: 1.767V CA
Entrada: 50Hz, 415 (opción 3) V CA
Salida: 1.767V CA
GMPU4 Entrada: 50Hz, 690V CA,
Salida: 1.767V CA
Catalogue Numbers |
Referencias | Referencias de catálogo
GMPU1, GMPU2, GMPU3
Aplicación:
- Se necesitan 3 acondicionadores de
alimentación para cada punto de detección de
tensión
- La máxima longitud de cable entre los
acondicionadores y la unidad de protección es
de 7m.
- Utilice cable AWG16 (1,5 mm²).
Esquema de ligações
|
Esquema de conexionado
Para sistemas de 3 fases a 4 fios Para sistemas de 3 Fases 4 hilos
|
VB
VC
1
2
1
EntelliGuard
EntelliGuard
---
---
3
4
3
L2
L3
conexión estrella
GND
2
---
---
4
N

Publicidad

loading