Configuring the Electronic trip unit (ETU) for
Voltage Conditioner:
Configure the trip unit (ETU) with following PT
ranges for Voltage conditioner catalogues listed..
GMPU1
PT voltage to be set to 230V
set
PT connection as Phase to Neutral
GMPU2
PT voltage to be set to 400V
set PT connection as Phase to Neutral
GMPU3
PT voltage to be set to 250/290/415V
..as per the jumper wire settings of J5
connector described below.
set PT connection as Phase to Neutral
and
GMPU4
PT voltage to be set to 690V
set PT connection as Phase to Phase
PT VOLTAGE
120
120
...save chosen value
J5 Connections GMPU3:
GMPU3 / 415V
Common
wire
250V
290V
415V
GMPU3 / 290V
Common
wire
250V
290V
415V
GMPU3 / 250V
Common
wire
250V
290V
415V
Fuse replacement
Substituição de fusível
1. Use screw driver to open the botton plate
2. Take out the bottom plate which carries the PCB
3. Now the fuse is accessible.
Replace the fuse if needed...
Configuração da unidade de disparo para o
acondicionador de alimentação:
Configure a unidade de protecção com os
seguintes valores de TENSÃO DE TRANSFORMADOR
para o acondicionador de alimentação escolhido
existente em catálogo
GMPU1
Ajustar TENSÃO DE TRANSFORMADOR A 230V
Ajustar CONEXÃO TRANSFORMADOR a Fase - Neutro
GMPU2
Ajustar TENSÃO DE TRANSFORMADOR A 400V
Ajustar CONEXÃO TRANSFORMADOR a Fase - Neutro
GMPU3
Ajustar TENSÃO DE TRANSFORMADOR A
250/290/415V
..dependendo da configuração do
conector J5 descrita mais abaixo.
Ajustar CONEXÃO TRANSFORMADOR a Fase - Neutro
GMPU4
Ajustar TENSÃO DE TRANSFORMADOR A 690V
Ajustar CONEXÃO TRANSFORMADOR a Fase - Fase
Tensão
690
120
Conexões J5, GMPU3:
GMPU3 / 415V
Comun
250V
290V
415V
GMPU3 / 290V
Comun
250V
290V
415V
GMPU3 / 250V
Comun
250V
290V
415V
1. Use uma chave de parafusos para abrir a tampa traseira
2. Retira a tampa traseira de acesso ao circuito electrónico
3. Agora o fusível está acessível.
Substitua o fusível se necessário...
1
ACCESSORIES
Configuración de la unidad de protección para el
acondicionador de alimentación:
Configure la unidad de protección con los
siguientes rangos TENSION TRAFOR para los
acondicionadores de alimentación existentes e
catálogo
GMPU1 Ajustar TENSION TRAFOR A 230V
GMPU2 Ajustar TENSION TRAFOR A 400V
GMPU3 Ajustar TENSION TRAFOR A 250/290/415V
.GMPU4 Ajustar TENSION TRAFOR A 690V
120
690
...Salvar valor escolhido
Conexionado de J5
GMPU3 / 415V
Común
cabo
250V
290V
415V
GMPU3 / 290V
Común
cabo
250V
290V
415V
GMPU3 / 250V
Común
cabo
250V
290V
415V
Cambio del fusible
1. Utilize un destornillador para abrir la tapa trasera
2. Saque la tapa trasera que contiene el circuito electrónico
3. Ahora es accesible el fusible.
Cámbielo si fuera necesario..
2
EntelliGuard G
Ajustar CONEX TRAFOR a Fase-Neutro
Ajustar CONEX TRAFOR a Fase-Neutro
..dependiendo de la configuración del
conector J5 descrita más abajo.
Ajustar CONEX TRAFOR a Fase-Neutro
Ajustar CONEX TRAFOR a Fase-Fase
TENSION
TRAFOR
120
690
120
....guardar valor elegido
cable
cable
cable
3
4
.4
4.4-19