13. Technical data
Supply voltage
•
3 x 230 V - 10 %/+ 6 %, 50 Hz.
•
3 x 400 V - 10 %/+ 6 %, 50 Hz.
Enclosure class
IP68, according to IEC 60529.
Insulation class
F (155 °C).
Pump curves
Pump curves are available via internet www.grundfos.com.
The curves are to be considered as a guide. They must not be
used as guarantee curves.
Test curves for the supplied pump are available on request.
It must be ensured that the pump does not operate outside the
recommended operating range during normal operation.
Power P
Power P
2
1
[kW]
[kW]
2.2
2.8
2.2
2.8
2.2
2.8
3
3.8
3
3.8
3
3.8
4
4.8
4
4.8
4
4.8
4
4.8
4
4.8
6.0
7.1
6.0
7.1
6.0
7.1
6.0
7.1
6.0
7.1
7.5
8.9
7.5
8.9
7.5
8.9
7.5
8.9
7.5
8.9
9.2
10.5
9.2
10.5
9.2
10.5
9.2
10.5
9.2
10.5
11
12.6
11
12.6
11
12.6
11
12.6
11
12.6
The supply cable resistance depends on the cable diameter.
Resistance per running metre of cable: 1.5 mm
Resistance per running metre of cable: 2.5 mm
2 pole-motor
Voltage
Thermal protection
[V]
3 x 220-240
Thermal switch
3 x 380-415
Thermal switch
3 x 400-415
Thermal switch
3 x 220-240
Thermal switch
3 x 380-415
Thermal switch
3 x 400-415
Thermal switch
3 x 220-240
Thermal switch
3 x 380-415
Thermal switch
3 x 380-415
Thermistor
3 x 400-415
Thermal switch
3 x 400-415
Thermistor
3 x 220-240
Thermal switch
3 x 380-415
Thermal switch
3 x 380-415
Thermistor
3 x 400-415
Thermal switch
3 x 400-415
Thermistor
3 x 220-240
Thermal switch
3 x 380-415
Thermal switch
3 x 380-415
Thermistor
3 x 400-415
Thermal switch
3 x 400-415
Thermistor
3 x 220-240
Thermal switch
3 x 380-415
Thermal switch
3 x 380-415
Thermistor
3 x 400-415
Thermal switch
3 x 400-415
Thermistor
3 x 220-240
Thermal switch
3 x 380-415
Thermal switch
3 x 380-415
Thermistor
3 x 400-415
Thermal switch
3 x 400-415
Thermistor
2
= 0.012 W
2
= 0.007 W
Pump noise emission < 70 dB(A)
•
Measurements were carried out on dry-installed pumps in a
closed system.
•
Sound power measurements were carried out according to
ISO 3743.
•
Sound power was calculated at a distance of 1 metre
according to ISO 11203.
The sound pressure level of the pump is lower than the limiting
values stated in the EC Council directive 2006/42/EC relating to
machinery.
Cable cross section
[mm
1.5
1.5
1.5
1.5
1.5
1.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
Cable connection
Conductors/
2
]
plug pins
7/7
7/7
7/7
7/7
7/7
7/7
10/10
10/10
10/10
7/10
7/10
10/10
10/10
10/10
7/10
7/10
10/10
10/10
10/10
7/10
7/10
10/10
10/10
10/10
7/10
7/10
10/10
10/10
10/10
7/10
7/10
31