Fault/error
CAN communication error
(CAN acknowledgement
error)
Two devices respond to
one control command
CAN communication error
(CAN bit stuff error)
CAN communication error
(CAN bit error and/or CAN
acknowledgement error)
If the problem cannot be remedied by any of these procedures, please contact relyon
plasma GmbH.
11
Environment
11.1
Disposal
Be mindful of the environment.
Used electrical and electronic equipment must not be disposed of along with normal
waste.
-
This device contains valuable materials that can be recycled. Take the device to a
suitable collection point.
Please return defective or replaced exchange modules to relyon plasma GmbH for
analysis. Please contact us before doing so.
12
Conformity/Standards
You can obtain the declarations of conformity through our website in the Downloads
section.
12.1
CE
We declare that this product conforms to CE standards.
The product name can be found on the device's name plate.
12.2
FCC
We declare that this product conforms to FCC standards.
This device is compliant with the FCC specifications from 'Part 15' and 'Part 18'.
36
Cause
No CAN address assigned
CAN address assigned twice
Terminator not activated
Several terminators activated
CANhigh and CANlow signals
interchanged
Rectification
Set an address at the Config port that
is unique and not equal to '0' (see
Points 5.7 and 7.7)
Set an address at the Config port that
is unique and not equal to '0' (see
Points 5.7 and 7.7)
Set PIN8 at the Config port on the
last device to 'ON' (see Points 5.7
and 7.7)
Set PIN8 at the Config port on the
last device only to 'ON' (see Points
5.7 and 7.7)
Observe the pin assignment as
described under Point 2.4.
BA-PZ3_i_ML / F0354902