CONFIGURATION MENU
CALIBRATION
page 2 of 2
Operator can calibrate analog signal inputs and outputs.
C UTION
4-20mA and 0-10VDC input signals are pre-calibrated at the factory. Only change the input
calibration if the factory settings are not sufficient.
Continued from previous page
Calibration
- GPD/LPD Calibration
- Signal Calibration
- GO TO CONFIG MENU
S Series FW 4.01.02 US and Canada 800.683.2378, International 904.641.1666 www.stenner.com
continued
Signal Calibration
- 4-20mA IN
- 0 - 10V IN
- 4-20mA OUT
Signal Calibration
- 4-20mA IN
- 0 - 10V IN
- 4-20mA OUT
Signal Calibration
- 0 - 10V IN
- 4-20mA OUT
- GO TO CAL MENU
To top of
Calibration menu
Connect pump to 4-20mA loop
using a process meter or powered transmitter
When pump indicates to input
4mA, bring loop to 4.0mA
(or desired level). Press ENTER.
4-20mA IN Set
Input 4mA
set
Connect pump to 0-10V loop
using a process meter or powered transmitter
When pump indicates to input
0V, bring loop to 0.0V (or
desired level). Press ENTER.
0 - 10V IN Set
Input 0V
set
Connect process meter to 4-20mA output signal
In 4mA Out Set, press the UP
or DOWN button to adjust the
signal until the meter reads
4.0. Press ENTER.
4mA OUT Set
0508
set
18
When pump indicates to input
20mA, bring loop to 20.0mA
(or desired level). Press ENTER.
4-20mA IN Set
Input 20mA
set
back
To Signal Calibration menu
When pump indicates to input
10V, bring loop to 10.0V (or
desired level). Press ENTER.
0 - 10V IN Set
Input 10V
set
back
To Signal Calibration menu
In 20mA Out Set, press the
UP or DOWN button to adjust
the signal until the meter
reads 20.0. Press ENTER.
20mA OUT Set
2584
adjust
back
set
To Signal Calibration menu