CONFIGURATION MENU
LEAK DETECT
The leak detecting components determine when solution is present in the pump
head. When a leak is detected, the tube icon will always appear on the display.
Program how the pump responds when a leak is detected:
1. Set the display alarm, TUBE LEAK, to appear on the screen.
2. Set the pump to stop or continue to run when TUBE LEAK appears.
3. Set a delay (in seconds) for #1 or #2 and/or to activate a relay.
Leak detect is accomplished by sensing conductivity between two metal clips in the tube housing cover. The leak detect
bracket and leak detect tube housing cover must be installed in order to use this option.
The alarm on leak detect is disabled by default. The delay for the alarm to activate is also set to zero by default.
Tip: The leak detect sensitivity is factory pre-set to distinguish between water and typical water treatment chemicals.
Adjust the sensitivity according to the specific chemical utilized in the application. Adjust with the potentiometer located
under the signal cover. Instruction for adjusting are located in Connections Leak Detect in this manual.
NAVIGATION
Moves up in a menu, toggles
between options, or increase a value
Holding the
or
button causes the numbers to change rapidly.
Configuration
- Tube Timer
- Reset Totalizer
- Leak Detect
Enter the number of seconds
between the time a leak is
detected and the time the
alarm is activated. Adjustable
from 0 to 999 seconds.
Select "Yes" to shut pump off in the
event of a leak detect alarm, "No" to
allow the pump to continue to run in
the event of a leak detect alarm.
S Series FW 4.01.02 US and Canada 800.683.2378, International 904.641.1666 www.stenner.com
continued
Moves down in a menu, toggles
between options, or decreases a value
Alarm on tube leak?
Yes
yes/no
set
Delay to activate
_ _ 0 Second(s)
adjust
set
back
Stop pump on alarm?
Yes
yes/no
set
Stop pump on alarm?
No
yes/no
set
www.stenner.com
22
Manual
%
Tube Leak
Moves one step back in
a menu, when permitted
Alarm on tube leak?
No
yes/no
set
Select "Yes" to enable the leak
detect alarm, "No" to disable the
leak detect alarm feature.
To Configuration menu
To Configuration menu
Manual
%
0
Sets a value in a menu
Leak detect alarm
not enabled. To