CONTROL MODES MENU
PULSE
page 2 of 2
The menu example illustrates Units in gallons. For liters, select Liters in the Configuration menu. When in Control
mode, liters are represented by P/L on the display.
NAVIGATION
Moves up in a menu, toggles
between options, or increase a value
Holding the
or
button causes the numbers to change rapidly.
Continued from previous page
Pulse
- Program Settings
- Alarm Settings
- Go to Main Menu
S Series FW 4.01.02 US and Canada 800.683.2378, International 904.641.1666 www.stenner.com
continued
Moves down in a menu, toggles
between options, or decreases a value
Pulse to Activate
_ _ _ 1 Pulse(s)
adjust
Pump Run Time
_ 20.0 Sec(s)
adjust
Meter Rate
_ _ _ 0.0000
adjust
Pump Speed
010 %
adjust
To Pulse menu
After settings are entered the display returns to the Pulse
menu and Alarm Settings can be programmed.
39
Moves one step back in
Sets a value in a menu
a menu, when permitted
Set the number of pulses or dry
contacts (1 to 9999) for the pump
to accumulate before activating.
set
Set the number of seconds (20.0
to 999.9) the pump is to run once
it activates. The minimum run
time is 20.0 seconds.
set
set
Set the meter pulse rate or contact
P/G
rate. The rate is used to totalize the
process flow for the display.
set
Set the speed percentage (1
to 100) the pump is to run
while it is activated.
set

Publicidad

loading