P11.09
P11.10
P11.11
P11.12
P11.13
P11 – Config. EQUIP 2
P11.14
P11.15
P11.16
P11.17
P11.18
Press ENTER to access the sub-menus
Reading and editing with keyboard or ECO card
The purge is used to drain condensed water from the compressor tank. This is performed through solenoid
valves. Before setting the time and purge interval, be sure to assign the relay output to "drain" function.
Open purge time. Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set to 'OFF' (i.e. no purge) or from 1 to 30 seconds
Open purge
(adjustable). Press 'ENTER'. The set value is stored in memory and the browser returns to P11.09.
Purge interval. Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set from 60 to 3600 seconds (adjustable). Press
'ENTER'. The set value is stored in memory and the browser returns to P11.10.
Air vent interv
Drain time in relief. Active only during relief time. Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set between 'OFF'
(that is, no drain) or between 1 and 30 seconds (adjustable). Press 'ENTER'. The set value is stored in memory and the
browser returns to P11.11.
Purge in Relief
Note: The equipment's position on the status diagram influences the purge interval!
- When the equipment is in "load" status, the drain cycle normally occurs, as configured in P11.09 and P11.10.
- When the equipment enters "relief" status, the purge time that has been interrupted is stored in memory, returning after
entering in "load" status.
Restraint of maximum number of starts per hour.
Each time the main motor starts, an inclusion event occurs in a perpetual FIFO list (first in, first out). In the interval of 3600
seconds (or 1 hour), for each additional start, up to the maximum number set, a new input is made. If the number of starts
reaches the maximum, a new relief time is calculated to allow an additional start, successively.
Note: this function only influences relief time and does not prevent the motor from starting. If a start request
Starts by hour
occurs after the maximum number of starts per hour, the last record is removed from the list of FIFO events,
forcing the relief time to increase.
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set between 'OFF' (that is, no limit) or between 1 and 20 starts per hour
(adjustable, with unit pitch). Press 'ENTER'. The set value is stored in memory and the browser returns to P11.12.
Restraint time for differential pressure (between outlet pressure and internal pressure in the air-oil separator). This func-
tion is used to filter or ignore sudden changes during the set time interval.
DifPres Delay
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set from 1 to 600 seconds (unit pitch). Press 'ENTER'. The set value is
stored in memory and the browser returns to P11.13.
Used to configure a variety of maintenance services 1.
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set between 'OFF' (that is, without scheduling) or between the
Maintenance hours 1
following services: air filter check, oil filter check, belt check, dust cleaning of compartment filters, oil change, separator
check, grease bearings, exhaust check, dryer check, electrical part check, lubrication, valve check, flow vs pressure and unit
check. Press 'ENTER'. The set value is stored in memory and the browser returns to P11.14.
Note: set the hours in parameter P16.01.
Used to configure a variety of maintenance services 2.
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set between 'OFF' (that is, without scheduling) or between the
Maintenance hours 2
following services: air filter check, oil filter check, belt check, dust cleaning of compartment filters, oil change, separator
check, grease bearings, exhaust check, dryer check, electrical part check, lubrication, valve check, flow vs pressure and unit
check. Press 'ENTER'. The set value is stored in memory and the browser returns to P11.15.
Note: set the hours in parameter P16.02.
Used to configure a variety of maintenance services 3.
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set between 'OFF' (that is, without scheduling) or between the
Maintenance hours 3
following services: air filter check, oil filter check, belt check, dust cleaning of compartment filters, oil change, separator
check, grease bearings, exhaust check, dryer check, electrical part check, lubrication, valve check, flow vs pressure and unit
check. Press 'ENTER'. The set value is stored in memory and the browser returns to P11.16.
Note: set the hours in parameter P16.03.
Used to configure a variety of maintenance services 4.
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set between 'OFF' (that is, without scheduling) or between the
Maintenance hours 4
following services: air filter check, oil filter check, belt check, dust cleaning of compartment filters, oil change, separator
check, grease bearings, exhaust check, dryer check, electrical part check, lubrication, valve check, flow vs pressure and unit
check. Press 'ENTER'. The set value is stored in memory and the browser returns to P11.17.
Note: set the hours in parameter P16.04.
Used to configure a variety of maintenance services 5.
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set between 'OFF' (that is, without scheduling) or between the
Maintenance hours 5
following services: air filter check, oil filter check, belt check, dust cleaning of compartment filters, oil change, separator
check, grease bearings, exhaust check, dryer check, electrical part check, lubrication, valve check, flow vs pressure and unit
check. Press 'ENTER'. The set value is stored in memory and the browser returns to P11.18.
Note: set the hours in parameter P16.05.
212