Stop time:
When the stop key
is pressed, the compressor will enter relief and the main motor will keep running during the stop time. This time
is necessary in order for the compressor's internal pressure to decrease before the compressor's full stop, avoiding possible oil backflow
through the compression unit and air filter. The stop time starts at the moment the compressor enters relief. If the compressor is already in
relief at the moment the stop key is pressed, the stop time will be reduced. If the compressor is already in standby mode, the stop time is
not applicable.
Auto restart time:
The Control I interface is equipped with a low voltage ( < 19.8V) and power drop (> 40ms) detector . If a voltage drop or shortage happens
when the equipment is working, the compressor will restart automatically when voltage is restored. Control I will show a tension drop alarm
to indicate that the fault happened.
To enable this function, select an auto restart time greater than zero. When the energy is reestablished, the interface will wait for the auto
restart time before it starts the motor. This time is necessary in order for the simultaneous starts of several different devices to be avoided,
when power is restored.
To disable the auto restart function, just set the auto restart time to zero.
4.2 Configuration Menu
ITEM
1
2.Sd
Star/delta time
2
2.Ad
Network address (RS 485 optional)
3
2.LS
Load source
4
2.SS
Start source
5
2.PA
High pressure alarm
6
2.PF
Overpressure
7
2.tA
High temperature alarm
8
2.tF
High temperature trip
9
2.d2
C2 (digital input 2) configuration
10
2.d3
C3 (digital input 3) configuration
11
2.d3
C4 (digital input 4) configuration
12
2.d5
C5 (digital input 5) configuration
13
2.d6
C6 (digital input 6) configuration
DESCRIPTION
25
RANGE
0.0 to 20.0 seconds
1 to 12
0=local, 1=RS485
0=local, 1=RS485
0.8 a 67.8bar
1.0 a 68.0bar
50 a 248°C
52 a 250°C
2: Eno - Error @ 24Vac (0Vac=OK)
3: Enc - Error @ 0Vac (24Vac=OK)
2: Eno - Error @ 24Vac (0Vac=OK)
3: Enc - Error @ 0Vac (24Vac=OK)
2: Eno - Error @ 24Vac (0Vac=OK)
3: Enc - Error @ 0Vac (24Vac=OK)
0: Ano - Alarm @ 24Vac (0Vac=OK)
1: Anc - Alarm @ 0Vac (24Vac=OK)
2: Eno - Error @ 24Vac (0Vac=OK)
3: Enc - Error @ 0Vac (24Vac=OK)
6: rSS - Remote start/stop (24Vac=Start)
0: Ano - Alarm @ 24Vac (0Vac=OK)
1: Anc - Alarm @ 0Vac (24Vac=OK)
2: Eno - Error @ 24Vac (0Vac=OK)
3: Enc - Error @ 0Vac (24Vac=OK)
4: rLu - oad/relief (24Vac=Load)
5: PSr - Pressure switch regulation
(24Vac=Load)
STANDARD(*)
5.0 segundos
1
0=local
0=local
7.6bar
8.0bar
110°C
120°C
standard
standard
standard
standard
standard