Main motor phase unbalance protection:
A priori, the measured voltage value for each phase must be equal. Unbalance protection measures any deviation from this condition. If the
measured value in any of the 3 phases deviates over the value set in P14.06 (percentage), the interface stops the compressor.
Protection by main motor phase angle:
No setup is required! The interface monitors the sequence of phases 1, 2 and 3 and the corresponding angles.
Phase L1 angle = 0°
Phase L2 angle = between 100° and 140°
Phase L3 angle = between 220° and 260°
If the phase angle error occurs, the interface will stop the compressor immediately.
Protection for current sensor or wiring interruption failure:
If the measured current falls below 20% of the rated current value when the motor is running, the interface will assume that there is an error in
the current sensor or wiring failure.
8.7 CONFIGURABLE MENUS
The interface has a number of configurable menus to restrict compressor malfunctions, as shown below.
Name
Code
P15.01*
P15.02
Impediments
P15.03
P15.04
P16.01
P16.02
Warning alarm
P16.03
P16.04
Press ENTER to access the sub-menus - *Editable only when the machine is stopped.
Reading and editing with keyboard or ECO card
Table 8.7.1 - Configurable Menus
Text
Additional information
This parameter is used so the operator can intentionally block the machine operation.
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set between ON and OFF. Press 'ENTER' again. The set value is stored
Operator
in memory and the browser
returns to P15.01.
For safety reasons, some equipment requires the door to be closed to release the operation. Blocking the operation can be
performed through a digital input (see instructions on setting up a digital input).
Open door
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set between ON and OFF. Press 'ENTER' again. The set value is stored
in memory and the browser
returns to P15.02.
Note: The digital input must be set to "open door".
For safety reasons, some equipment requires the door to be closed to release the operation. Blocking the operation can be
performed through a digital input (see instructions on setting up a digital input).
Low Temperature
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set between ON and OFF. Press 'ENTER' again. The set value is stored
in memory and the browser
returns to P15.02.
Note: The digital input must be set to "open door".
This parameter is used to prevent the compressor from starting when the internal pressure is too high.
For this operation, the compressor must have a pressure sensor installed in the internal air/oil tank. If this sensor isn't
available, this parameter must be disabled.
High INT PRESS
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set between 0.1BAR and 2.0BAR (in BAR or other selected pressure
unit). Press 'ENTER' again. The set value is stored in memory and the browser returns to P15.04.
Setup of ALARMS and WARNINGS and immediate stop conditions by ALARMS.
It is recommended to set this parameter to control the maintenance frequency for the air filter.
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set from 0 to 10,000 hours (100-hour pitch). The default value is 2,000
Air filter maint.
hours.
Press 'ENTER' again. The set value is stored in memory and the browser returns to P16.01.
Note: you need to enable the parameter in menu P11 - equipment settings.
It is recommended to set this parameter to control the maintenance frequency for the oil filter.
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set from 0 to 10,000 hours (100-hour pitch). The default value is 2,000
Oil filter maint.
hours.
Press 'ENTER' again. OThe set value is stored in memory and the browser returns to P16.02.
Note: you need to enable the parameter in menu P11 - equipment settings.
It is recommended to set this parameter to control the maintenance frequency for the air/oil separator.
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set from 0 to 10,000 hours (100-hour pitch). The default value is 2,000
Separator maint.
hours.
Press 'ENTER' again. The set value is stored in memory and the browser returns to P16.03.
Note: you need to enable the parameter in menu P11 - equipment settings.
It is recommended to set this parameter to control the maintenance frequency to grease the bearings/bearing of the main
motor.
MTR grease maint.
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set from 0 to 10,000 hours (100-hour pitch). The default value is 2,000
hours.
Press 'ENTER' again. The set value is stored in memory and the browser returns to P16.04.
Note: you need to enable the parameter in menu P11 - equipment settings.