Press ENTER to access the sub-menus - *Editable only when the machine is stopped
Read-Only
Reading and editing with keyboard or ECO card
Pres target VSD
Reference pressure for variable speed compressor.
Maximum speed. Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set between 100 and 10000 RPM (pitch 100 RPM).
MAX VSD Speed
Press 'ENTER'. The set value is stored in memory and the browser returns to P13.03.
Minimum speed. Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set between 0 and 9900 RPM (pitch 100 RPM). Press
MIN VSD Speed
'ENTER'. The set value is stored in memory and the browser returns to P13.04.
Optimal speed. Press 'ENTER'. Set between 100 and 10000 RPM (pitch 100 RPM). Press 'ENTER'. The set value is stored in
memory and the browser returns to P13.05.
OPT VSD Speed
Note: The optimal speed is used as information by the 485 network.
Compressor speed during relief. Press 'ENTER'. Set between 0 and 9900 RPM (pitch 100 RPM). Press 'ENTER'. The set
VSD relief SPEED
value is stored in memory and the browser returns to P13.06.
VSD RPM Speed
RPM speed signal for the drive. Non-editable. It is the PID output, which goes to the inverter.
VSD Output CURR
Current signal to drive. Non-editable.
Proportional value P, from PID controller (see diagram below).
Press 'ENTER'. Set between 0 and 100. Press 'ENTER'. The set value is stored in memory and the browser returns to
P13.09.
Const P VSD
Integral value I from PID controller (see diagram above).
Const I VSD
Press 'ENTER'. Set between 0 and 100. Press 'ENTER'. The set value is stored in memory and the browser returns to
P13.10.
Derivative value D from PID controller (see diagram above).
Const D VSD
Press 'ENTER'. Set between 0 and 100. Press 'ENTER'. The set value is stored in memory and the browser returns to
P13.11.
VSD Speed %
Compressor's percentage speed. Non-editable.
Maximum acceleration ramp. Press 'ENTER'. Set between 5% and 100% (pitch 1%). Press 'ENTER'. The set value is stored
VSD max acl ramp
in memory and the browser returns to P13.13.
Line lim speed
-
Set lower limit of range 1 of frequencies to be avoided (Hz1-lower). Press 'ENTER'. Set between OFF and 100Hz (unit step).
Press 'ENTER' again. The set value is stored in memory and the browser returns to P13.25.
Avoid freq. Hz 2 low
Notes:
When frequency band 1 is set to a value other than OFF, the remaining parameters appear. There are 3 fre-
quency range settings (Hz1, Hz2 and Hz3).
Set upper limit of range 1 of frequencies to be avoided (Hz1-upper). Press 'ENTER'. Set between Hz1-lower and 100Hz (unit
Avoid freq. Hz 1 high
pitch). Press 'ENTER' again. The set value is stored in memory and the browser returns toP13.26
Set lower limit of range 2 of frequencies to be avoided (Hz2-lower). Press 'ENTER'. Set between OFF and 100Hz (unit pitch).
Avoid freq. Hz 2 low
Press 'ENTER' again. The set value is stored in memory and the browser returns to P13.27.
Set upper limit of range 2 of frequencies to be avoided (Hz2-upper). Press 'ENTER'. Set between Hz2-lower and 100Hz (unit
Avoid freq. Hz 2 high
pitch). Press 'ENTER' again. The set value is stored in memory and the browser returns to P13.28.
Set lower limit of range 3 of frequencies to be avoided (Hz3-lower). Press 'ENTER'. Set between OFF and 100Hz (unit pitch).
Avoid freq. Hz 3 low
Press 'ENTER' again. The set value is stored in memory and the browser returns to P13.29.
Set upper limit of range 3 of frequencies to be avoided (Hz3-upper). Press 'ENTER'. Set between Hz3-lower and 100Hz (unit
Avoid freq. Hz 3 high
pitch). Press 'ENTER' again. The set value is stored in memory and the browser returns to P13.30.
215