Warning alarm
P16.22
P16.23
P16.24
P16.25
P16.26
P16.27
P16.28
P16.29
Press ENTER to access the sub-menus - *Editable only when the machine is stopped.
Reading and editing with keyboard or ECO card
High differential pressure warning (internal pressure minus outlet pressure). Press 'ENTER'. Use the 'UP' and 'DOWN'
buttons to set the values off, 0.1 bar and the maximum value allowed. Press 'ENTER'. The selected value will be stored
and the screen will return to the previous menu.
Note: - The minimum difference between the alarm value and the error value for the differential pressure is
Differential pressure
0.2bar.
- Differential pressure monitoring is disabled if the discharge temperature is lower than 50°C.
- The differential pressure error will only be enabled if the value is above the set value for more than 10
seconds.
High differential pressure warning for oil/air separator. Press 'ENTER'. Use the 'UP' and 'DOWN' buttons to set between
off, 0.01 bar and 2.00 bar. Press 'ENTER'. The selected value will be stored and the screen will return to the previous
menu.
DP separad elev
Note: Differential pressure monitoring is disabled if the discharge temperature is lower than 50°C.
Note: differential pressure error will only be enabled if the value is above the set value for more than 10
seconds.
Power supply voltage warning. Press 'ENTER'. Use the 'UP' and 'DOWN' buttons to set between off and on. The selected
value will be stored and the screen will return to the previous menu.
Phase detection
If turned on, this parameter will display a warning if a phase failure occurs or if the frequency is below 40Hz or greater
than 70Hz for more than 0.5 seconds.
Maximum number of main motor starts per hour. Press 'ENTER'. Use the 'UP' and 'DOWN' buttons to set between off, 1 to
Starts by hour
20. The selected value will be stored and the screen will return to the previous menu.
Open door warning.
Open door
Press 'ENTER'. Use the 'UP' and 'DOWN' buttons to set between Off or On. Press 'ENTER'. The selected value will be
stored and the screen will return to the previous menu.
Note: requires association with a digital input. Check P18 menu.
High differential pressure warning on cabinet air input filter.
DP CAB filter
Press 'ENTER'. Use the 'UP' and 'DOWN' buttons to set between Off or On. Press 'ENTER'. The selected value will be
stored and the screen will return to the previous menu.
Note: requires association with a digital input. Check P18 menu.
High differential pressure warning on air filter.
Air Filter DP
Press 'ENTER'. Use the 'UP' and 'DOWN' buttons to set between Off or On. Press 'ENTER'. The selected value will be
stored and the screen will return to the previous menu.
Note: requires association with a digital input. Check P18 menu.
High differential pressure warning on oil filter.
DP oil filter
Press 'ENTER'. Use the 'UP' and 'DOWN' buttons to set between Off or On. Press 'ENTER'. The selected value will be
stored and the screen will return to the previous menu.
Note: requires association with a digital input. Check P18 menu.
High differential pressure warning on oil filter.
DP separator
Press 'ENTER'. Use the 'UP' and 'DOWN' buttons to set between Off or On. Press 'ENTER'. The selected value will be
stored and the screen will return to the previous menu.
Note: requires association with a digital input. Check P18 menu.
Fan motor alarm warning.
Motor fan alarm
Press 'ENTER'. Use the 'UP' and 'DOWN' buttons to set between Off or On. Press 'ENTER'. The selected value will be
stored and the screen will return to the previous menu.
Note: requires association with a digital input. Check P18 menu.
Fan motor alarm warning.
Purge Alarm
Press 'ENTER'. Use the 'UP' and 'DOWN' buttons to set between Off or On. Press 'ENTER'. The selected value will be
stored and the screen will return to the previous menu.
Note: requires association with a digital input. Check P18 menu.
Alarm warning on the cold-water system.
COLD water alarm
Press 'ENTER'. Use the 'UP' and 'DOWN' buttons to set between Off or On. Press 'ENTER'. The selected value will be
stored and the screen will return to the previous menu.
Note: requires association with a digital input. Check P18 menu.
Low oil level warning.
Oil level alarm
Press 'ENTER'. Use the 'UP' and 'DOWN' buttons to set between Off or On. Press 'ENTER'. The selected value will be
stored and the screen will return to the previous menu.
Note: requires association with a digital input. Check P18 menu.
Alarm warning on air dryer.
Dryer alarm
Press 'ENTER'. Use the 'UP' and 'DOWN' buttons to set between Off or On. Press 'ENTER'. The selected value will be
stored and the screen will return to the previous menu.
Note: requires association with a digital input. Check P18 menu.
High differential pressure warning on pre-filter.
ALM DP Pre-FLT
Press 'ENTER'. Use the 'UP' and 'DOWN' buttons to set between Off or On. Press 'ENTER'. The selected value will be
stored and the screen will return to the previous menu.
Note: requires association with a digital input. Check P18 menu.