Variable speed settings for inverter and main electric motor.
Setup FLEX
P13.01*
Press ENTER to access the sub-menus - *Editable only when the machine is stopped
Reading and editing with keyboard or ECO card
Setting relief hours. It is typically used to clear the hours before the technical start or to synchronize with another external
timer.
Adjust relief HRS
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set the value. Press 'ENTER'. The set value is stored in memory and the
browser returns to P12.10.
Setting stopped hours. It is typically used to clear the hours before the technical start or to synchronize with another
external timer.
Adjust stopped HRS
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set the value. Press 'ENTER'. The set value is stored in memory and the
browser returns to P12.11.
Setting the analog input sensor type 3. Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to select between 'PT1000',
'PT100', 'KTY' or digital. Press 'ENTER'. The set value is stored in memory and the browser returns to P12.12.
Sensor EA3 type
Note:
- it is recommended the use of PT100 or PT1000 temperature sensors;
- when using KTY sensor, it should be 2000 Ohms @ 25ºC.
Setting the analog input sensor type 5. Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to select between 'PT1000',
'PT100', 'KTY' or digital. Press 'ENTER'. The set value is stored in memory and the browser returns to P12.13.
Sensor EA5 type
Note:
- it is recommended the use of PT100 or PT1000 temperature sensors;
- when using KTY sensor, it should be 2000 Ohms @ 25ºC.
Compressor internal pressure sensor. When installed, its use and function must be enabled in conjunction with the outlet
pressure sensor.
SENS PRESS INT
Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set the value. Press 'ENTER'. The set value is stored in memory and the
browser returns to P12.14.
Enables the GCI menu (integrated compressor manager). Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set the desired
value. Press 'ENTER'. The set value is stored in memory and the browser returns to P12.15.
Enable GCI menu
When enabled, P80, P81, and P82 menus are available for setup.
Note: menu P12.15 is merely for enabling this item. Once enabled, you must configure the GCI function in
menus P80, P81 and P82.
Pressure sensor range for GCI function. Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set the desired value. Press
PRESS GCI SENS Range
'ENTER'. The set value is stored in memory and the browser returns to P12.16.
Setting fan operating temperature (high temperature). Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set the desired
value. Press 'ENTER'. The set value is stored in memory and the browser returns to P12.17.
PRESS GCI SENS Range
Note: When the 'compressor output temperature' ≥ 'fan operating temperature', the output relay with 'cooling'
function is enabled.
Setting fan off temperature (low temperature). Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set the desired value.
Press 'ENTER'. The set value is stored in memory and the browser returns to P12.18.
Temp fan off
Note: when the 'compressor output temperature' ≤ 'fan off temperature', the output relay with 'cooling'
function is turned off.
Minimum fan on time. Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set the desired value from 0 to 600 seconds (unit
Min. Time fan on
pitch). Press 'ENTER'. The set value is stored in memory and the browser returns to P12.19.
Opening screen
Enables or disables the setting for the opening screen.
SETUP P00.03
Setting up display of user menus. Press 'ENTER' to access the P00.03 setup sub-menu.
Sel. Menu page
Selecting the menu page on the opening screen, P00.03.
Sel. Menu item
Selecting the menu item on the opening screen, P00.03.
SETUP P00.04
Setting up display of user menus. Press 'ENTER' to access the P00.04 setup sub-menu.
Sel. Menu page
Selecting the menu page on the opening screen, P00.04.
Sel. Menu item
Selecting the menu item on the opening screen, P00.04.
SETUP P00.05
Setting up display of user menus. Press 'ENTER' to access the P00.05 setup sub-menu.
Sel. Menu page
Selecting the menu page on the opening screen, P00.05.
Sel. Menu item
Selecting the menu item on the opening screen, P00.05.
Speed control mode (variable or fixed). Press 'ENTER'. Use the 'UP' and 'DOWN' arrows to set between 'VARIABLE' and
'FIXED'. Press 'ENTER'. The set value is stored in memory and the browser returns to P13.01.
Notes:
VSD control mode
- in "variable speed" control mode, the compressor will operate in the set speed range;
- in "fixed speed" control mode, the compressor will operate in only two speeds: optimum speed (low pressu-
re) and relief speed (high pressure), similar to an electronic gear.