Signal targets for CU_STW1
Signal
Meaning
CU_STW1.0
Central measuring probe, synchronizing signal source
CU_STW1.1
RTC real time synchronization PING
CU_STW1.2
ESR-Trigger
CU_STW1.3
Reserved
CU_STW1.4
Reserved
CU_STW1.5
Reserved
CU_STW1.6
Reserved
CU_STW1.7
1. Acknowledge faults
CU_STW1.8
Reserved
CU_STW1.9
Reserved
CU_STW1.10
Acknowledgment automatically suppressed
CU_STW1.11
Reserved
CU_STW1.12
Master sign-of-life bit 0
CU_STW1.13
Master sign-of-life bit 1
CU_STW1.14
Master sign-of-life bit 2
CU_STW1.15
Master sign-of-life bit 3
<1> Used in telegrams 390 to 394.
<2> Only available when the function module "Extended setpoint channel" is active (r0108.9 = 1).
1
2
DO: CU_G, CU_S
PROFIdrive - CU_STW1 control word 1, Control Unit interconnection
<2>
3
4
Interconnection
[Function diagram]
[Function diagram]
parameters
internal control word
signal target
p0681[0] = r2090.0
-
p3104 = r2090.1
-
p0890.0 = r2090.2
-
-
-
-
-
-
-
-
-
p2103[0] = r2090.7
-
-
-
-
-
p3116 = r2090.10
-
-
-
p2045 = r2050[0]
-
5
6
fp_2495_54_eng.vsd
27.06.13 V05.02.03
PROFIdrive sampling time
<1>
Inverted
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7
8
Function diagram
- 2495 -
S120/S150/G130/G150