Descargar Imprimir esta página

YASKAWA LA700 Serie Instrucciones De Instalación Y Funcionamiento página 362

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 160
10 Attachment
WARNING
Electrical Shock Hazard. Do not ground the main circuit bus. Incorrect wiring can cause serious injury or
death.
Note:
• Install a fuse for each drive when operating more than one drive. If one fuse blows, replace all fuses.
• Install the external filter (system) to comply with the EMC Directive.
Refer to
Table 10.13
and
Drive Model
2022
2031
2041
2059
2075
2094
FWH-300A
2110
FWH-275A
2144
FWH-350A
*1
Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
Drive Model
4012
4019
4023
4030
4039
4049
4056
4075
4094
4114
*1
Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
362
Figure 10.8 Wiring Example for DC Power Supply Input
Table 10.14
for the recommended fuses.
Table 10.13 Recommended Fuse (Three-Phase 200 V Class)
Fuse
Manufacturer: Bussmann
Model
Qty
FWH-80B
2
FWH-125B
2
FWH-150B
2
FWH-200B
2
FWH-250A
2
FWH-250A
2
*1
FWH-250A
2
*1
FWH-300A
2
*1
Table 10.14 Recommended Fuse (Three-Phase 400 V Class)
Fuse
Manufacturer: Bussmann
Model
Qty
FWH-60B
2
FWH-80B
2
FWH-90B
2
FWH-150B
2
FWH-200B
2
FWH-200B
2
FWH-225A
2
FWH-250A
2
FWH-275A
2
FWH-275A
2
Drive Model
2181
2225
2269
2354
2432
2519
Drive Model
4140
4188
4225
4270
4325
4380
YASKAWA TOMPYEULA7002A LA700 Series Installation and Operation Instruction
Fuse
Manufacturer: Bussmann
Model
Qty
FWH-350A
2
*1
FWH-450A
FWH-450A
2
*1
FWH-600A
FWH-600A
2
*1
FWH-700A
FWH-800A
2
*1
FWH-1000B
FWH-1000B
2
FWH-1000B
2
Fuse
Manufacturer: Bussmann
Model
Qty
FWH-300A
2
*1
FWH-325A
FWH-400A
2
*1
FWH-450A
FWH-500A
2
*1
FWH-600A
FWH-600A
2
*1
FWH-700A
FWH-700A
2
*1
FWH-800A
FWH-800A
2
*1
FWH-1000B

Publicidad